5 Configuration
P153/EN M/B
5-105
2.4.23 Group 1- Thermal Overload Submenu
2.4.23.1 View/Edit Settings (If Characteristics is disabled)
4
Characteristic
Disabled
THERMAL OVERLOAD
GROUP 1
4 3
3- - -4
3
For Save
CLEAR For Cancel
4
SAVE Settings
3
CLEAR
DISCARD Settings
EDIT
(*)
(*)
Note: (*) indicates Edit key used to modify settings. Refer to the View and Edit settings section.
2.4.23.2 View/Edit Settings (If Characteristics is set as Single)
Thermal Trip
1.00
A
Thermal Alarm
70 %
3 4 3 4
Time Constant 1
10
3 4
K
1.05
3 4
Characteristic
Single
THERMAL OVERLOAD
4
GROUP 1
6
4 3
3- - -4
3 For Save
CLEAR For Cancel
4
SAVE Settings
3
CLEAR
DISCARD Settings
EDIT
(*)
(*)
(*)
(*)
(*)
Note: (*) indicates Edit key used to modify settings. Refer to the View and Edit settings section.