Test LEDs
No Operation
Editable setting
By using the (5) or (6) key, Test LEDs can be set for No Operation /
Apply Test.
2.3.16 Group 1 Menu
2.3.16.1 Edit Settings
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
SYSTEM CONFIG
Password protected window for System Configuration i.e. 2nd
Harmonic (Disabled/Enabled), 2ndHarm Thresh and I>lift 2H.
Note: Setting will be seen only when it is enabled in Configuration
OVERCURRENT
Password protected window for Overcurrent i.e. I>1 Function, I>2
Function and I>3 Function. The functions can be set as Disabled / DT /
IDMT.
Note: Setting will be seen only when it is enabled in Configuration
NEG SEQUENCE O/C
Password protected window for
Function, I2>2 Function and I2>3 Function. The functions can be set as
Disabled / DT / IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.
BROKEN CONDUCTOR
Password protected window for
i.e. BC Alarm
(Enable/Disabled), I2/I1 Setting - 1 and I2/I1 Time Dly – 1, BC Trip
(Enable/Disabled), I2/I1 Setting - 2 and I2/I1 Time Dly - 2.
EARTH FAULT 1
Password protected window for Earth Fault 1 (measured) i.e. IN1>1
Function, IN1>2 Function and IN1>3 Function. The functions can be set
as Disabled / DT / IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.
EARTH FAULT 2
Password protected window for
(derived)
i.e. IN2>1
Function, IN2>2 Function and IN2>3 Function. The functions can be set
as Disabled / DT / IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.
THERMAL OVERLOAD
Password protected window for Thermal Overload i.e. Characteristic
(Disabled/Single), Thermal Trip, Thermal Alarm, Time Constant 1 and K.
Note: Setting will be seen only when it is enabled in Configuration
setting.