P50 Agile P153
5 Configuration
P153/EN M/B
5-57
I< Status
Disabled
Editable setting
By using the (5) or (6) key, I< Status can be Enabled / Disabled.
2.3.16.10.2
Edit Settings
(If I< Status is enabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
UNDERCURRENT
Password protected window for Undercurrent i.e. I< Status, I< and tI<.
I< Status
Enabled
Editable setting
By using the (5) or (6) key, I< Status is Enabled.
I<
1.00 A
Editable setting
By using the (5) or (6) key, I< settings can be set. The setting range is
from 0.1 to 1 In in steps of 0.01 In.
t I<
1.00 S
Editable setting
By using the (5) or (6) key, t I<setting can be set. The setting range is
from 0.2 to 100s in steps of 0.01s
2.3.16.11 Group 1 CB Fail Submenu
2.3.16.11.1
Edit Settings
(If CB Fail Status is disabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
CB FAIL
Password protected window for CB FAIL i.e. CB Fail Status, CB Fail
Timer, CB Reset, I<, IN<, Remove I> Start and Remove IN> Start.
CB Fail Status
Disabled
Editable setting
By using the (5) or (6) key, CB Fail Status can be Enabled /
Disabled