EasyManua.ls Logo

GE Agile P50 Series - 2.3.16.5 Group1 -Broken Conductor Submenu; 2.3.16.5.1 Edit Settings (if function is disabled); 2.3.16.5.2 Edit Settings (if function is enabled)

GE Agile P50 Series
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P50 Agile P153
5 Configuration
P153/EN M/B
5-42
2.3.16.5 Group1 Broken Conductor Submenu
2.3.16.5.1
Edit Settings
(if function is disabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
BROKEN CONDUCTOR
Password protected window for Broken Conductor i.e. BC Alarm
(Enable/Disabled), I2/I1 Setting - 1 and I2/I1 Time Dly – 1, BC Trip
(Enable/Disabled), I2/I1 Setting - 2 and I2/I1 Time Dly - 2.
BC Alarm
Disabled
Editable setting
By using the (+ /5) or (- /6) key, BC Alarm is Disabled.
BC Trip
Disabled
Editable setting
By using the (+ /5) or (- /6) key, BC Trip is Disabled.
2.3.16.5.2
Edit Settings
(if function is enabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
BROKEN CONDUCTOR
Password protected window for Broken Conductor i.e. BC Alarm
(Enable/Disabled), I2/I1 Setting - 1 and I2/I1 Time Dly – 1, BC Trip
(Enable/Disabled), I2/I1 Setting - 2 and I2/I1 Time Dly - 2.
BC Alarm
Enabled
Editable setting
By using the (5) or (6) key, BC Alarm is Enabled.
I2/I1Set-1
0.50
Editable setting
By using the (5) or (6) key, I2/I1 Set-1 can be set. The setting range is
from 0.20 to 1.00 in steps of 0.01

Table of Contents

Related product manuals