2.3.16.5 Group1 –Broken Conductor Submenu
2.3.16.5.1
Edit Settings
(if function is disabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
BROKEN CONDUCTOR
Password protected window for Broken Conductor i.e. BC Alarm
(Enable/Disabled), I2/I1 Setting - 1 and I2/I1 Time Dly – 1, BC Trip
(Enable/Disabled), I2/I1 Setting - 2 and I2/I1 Time Dly - 2.
BC Alarm
Disabled
Editable setting
By using the (+ /5) or (- /6) key, BC Alarm is Disabled.
BC Trip
Disabled
Editable setting
By using the (+ /5) or (- /6) key, BC Trip is Disabled.
2.3.16.5.2
Edit Settings
(if function is enabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, BROKEN
CONDUCTOR, EARTH FAULT 1, EARTH FAULT 2, THERMAL
OVERLOAD, COLD LOAD PICKUP, UNDERCURRENT and CB FAIL.
Note: Group 1 Setting will be seen only when it is enabled in
Configuration setting.
BROKEN CONDUCTOR
Password protected window for Broken Conductor i.e. BC Alarm
(Enable/Disabled), I2/I1 Setting - 1 and I2/I1 Time Dly – 1, BC Trip
(Enable/Disabled), I2/I1 Setting - 2 and I2/I1 Time Dly - 2.
BC Alarm
Enabled
By using the (5) or (6) key, BC Alarm is Enabled.
I2/I1Set-1
0.50
Editable setting
By using the (5) or (6) key, I2/I1 Set-1 can be set. The setting range is
from 0.20 to 1.00 in steps of 0.01