13 Technical Specifications
P50 Agile P153
13-8
P153/EN M/B
1.2
Dielectric voltage
withstand test
IEC 60255-27:2005
(incl. corrigendum 2007)
1) 2kV rms for 1 minute between all terminals connected together with case earth.
2) 2kV rms for 1 minute between independent circuits with case earth.
3) 1.5kV rms for 1 minute across open contacts of changeover output relays.
1.3
Insulation resistance
test
IEC 60255-27:2005
(incl. corrigendum 2007)
> 100 MΩ at 500V DC
1.4
Creepage distances
and clearances
IEC 60255-27:2005
(incl. corrigendum 2007)
Pollution degree : 2
Overvoltage category : III