Programming Site Data 2-29
September 2004
Setting Up the Analog
Output Scale (cont.)
5. At BASE, enter a flow rate value for the low end of the analog
output range by using the arrow keys. Press [
W] and [X] to move
the cursor to desired location and press
[S] and [T] to increase
or decrease the number and press [ENTER].
6. At FULL, enter a flow rate value for the high end of the analog
output range by using the arrow keys. Press [
W] and [X] to move
the cursor to desired location and press
[S] and [T] to increase
or decrease the number and press [ENTER].
7. At Error handling, press [
X] to select the desired option for
handling errors (HOLD, LOW, HIGH, or OTHER) and press [ENTER].
8. If OTHER is selected, the Forced milliamps display appears. This
allows the user to impose a set value for this option. Enter the
desired forced milliamps by using the arrow keys. Press [
W] and
[
X] to move the cursor to desired location and press [S] and
[T] to increase or decrease the number and press [ENTER].
Procedure Options After completing the above steps, the user program returns to the
Global I/O window. Do one of the following:
• To continue regular programming, refer to Appendix A, Menu
Maps, to navigate to the desired menu.
• To leave the user program, press [ESC] four times.