Communicating with the OPTICA Using Ethernet G-3
January 2006
Determining the Available
Commands (cont.)
<OpticaAPI>SetSerialData</OpticaAPI>
<OpticaAPI>SetSupportedBaudRate</OpticaAPI>
<OpticaAPI>SetSupportedDataBits</OpticaAPI>
<OpticaAPI>SetSupportedSerialDataFormat</OpticaAPI>
<OpticaAPI>SetUserDefinedEquations</OpticaAPI>
</OpticaAPIInfo>
Retrieving the Alarm
Settings
Command:
http://3.112.160.36:28005/OpticaAPI.xml?GetAlarmData+0
Function Name: GetAlarmData
Channel: 0
Response:
<?xml version="1.0" encoding="UTF-8" standalone="yes" ?>
<OpticaAPIReturn Function="GetAlarmData">
<channel>0</channel>
<AlarmType>2</AlarmType>
<Enabled>true</Enabled>
<UnitOffset>2</UnitOffset>
<type>2</type>
<LowerLimit>30.000000</LowerLimit>
<UpperLimit>60.000000</UpperLimit>
<AlarmType>2</AlarmType>
<Enabled>true</Enabled>
<UnitOffset>17</UnitOffset>
<type>17</type>
<LowerLimit>18.000000</LowerLimit>
<UpperLimit>26.000000</UpperLimit>
<retval>GEIAPI_SUCCESS</retval>
</OpticaAPIReturn
The Optica supports two alarm set points: The above response shows
the settings for alarm 1 and alarm 2 in that order. (Note that the index
is referenced from 0 , not 1). Alarm 1 parameters are described below.
Alarm 1 Settings: Alarm type = 2
(SetPoint, InnerBand, Outerband, Control, Service, Pacer)
2 here indicates Outerband
Enabled = True (Alarm 1 is enabled.)
Unit Offset = 2 (% RH)
See the Optica manual or use the GetHTPLabels for the list of
available units and the order.
Type = 2 ( ignore this value)
LowerLimit = 18.000000 (the Lower limit is 18 %RH)
UpperLimit = 26.000000 (The Upper limit is 26 %RH)