CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL 5–25
When the Analog Output parameter is set to “Serial Control”, the analog output(s)
reflect a value in proportion to the serial value written to a specific register within the
PQMII memory map. The locations are as described in the table below.
5.3.3 Analog Input
PATH: SETPOINTS ÖØ S2 SYSTEM SETUP ÖØ ANALOG INPUT
Analog Output Modbus Register Register
Analog Output 1 Analog Output 1 Serial Value 1067
Analog Output 2 Analog Output 2 Serial Value 106F
Analog Output 3 Analog Output 3 Serial Value 1077
Analog Output 4 Analog Output 4 Serial Value 107F
ANALOG INPUT [Z] ANALOG IN MAIN/ALT
SELECT RELAY: OFF
Range: Aux1, Aux2, Aux3, Off.
MESSAGE
ANALOG IN MAIN NAME:
MAIN ANALOG INPUT
Range: 20 alphanumeric characters
MESSAGE
ANALOG IN MAIN
UNITS: Units
Range: 10 alphanumeric characters
MESSAGE
MAIN 4 mA VALUE:
0
Range: 0 to 65000 in steps of 1
MESSAGE
MAIN 20 mA VALUE:
0
Range: 0 to 65000 in steps of 1
MESSAGE
ANALOG IN MAIN:
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
ANALOG IN MAIN LEVEL:
100 Units
Range: 0 to 65000 in steps of 1
MESSAGE
ANALOG IN MAIN
DELAY: 10.0 s
Range: 0.5 to 600.0 s in steps of 1
MESSAGE
ANALOG IN ALT NAME:
ALT ANALOG INPUT
Range: 20 alphanumeric characters
MESSAGE
ANALOG IN ALT
UNITS: Units
Range: 10 alphanumeric characters
MESSAGE
ALT 4 mA VALUE:
0
Range: 0 to 65000 in steps of 1
MESSAGE
ALT 20 mA VALUE:
0
Range: 0 to 65000 in steps of 1
MESSAGE
ANALOG IN ALT:
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
ANALOG IN ALT LEVEL:
100
Range: 0 to 65000 in steps of 1
MESSAGE
ANALOG IN ALT
DELAY: 10.0 s
Range: 0.5 to 600.0 s in steps of 1