CHAPTER 3: OPERATION
PQMII POWER QUALITY METER – INSTRUCTION MANUAL 3–5
The RESET key, along with the ENTER key, is also used to remove user defined default
messages. Refer to 3.4: Default Messages further details.
3.3.6 Message Keys
Use the MESSAGE keys to move between message groups within a page. The MESSAGE
DOWN
key moves toward the end of the page and the MESSAGE UP key moves toward the
beginning of the page. A page header message will appear at the beginning of each page
and a page footer message will appear at the end of each page. To enter a subgroup,
press the
MESSAGE RIGHT key. To back out of the subgroup, press the MESSAGE LEFT key.
Aux Relay
RESET NOT POSSIBLE
AUX CONDITION
EXISTS
Auxiliary LED indicator(s) and
aux relay(s) remain on
because condition is still
present
Alarm and Aux Relay
RESET NOT POSSIBLE
AUX CONDITION
EXISTS
Auxiliary and Alarm LED
indicators and alarm and aux
relays remain on because
condition is still present
Latched Alarm
(condition no longer
exists)
None
No message displayed, and
Alarm LED indicators and the
alarm relay turned off
Latched Aux Relay
(condition no longer
exists)
None
No message displayed, and
appropriate Auxiliary LEDs
and auxiliary relay(s) turned
off
Alarm and Latched Aux
Relay (Aux condition no
longer exists)
None
No message displayed, and
appropriate Auxiliary LEDs
and auxiliary relay(s) turned
off
Aux Relay and Latched
Alarm (alarm condition
no longer exists)
None
No message displayed, and
Alarm LEDs and alarm relay
turned off
Table 3–1: Reset Key Actions