APPENDIX A
PQMII POWER QUALITY METER – INSTRUCTION MANUAL A–5
A.1.5 Additions to Modbus Memory Map
The following two sections are added to the Modbus Memory Map for Mod 506. For
additional information on Modbus, refer to 7.4: DNP 3.0 Communications.
The following memory map format has also been added:
GROUP
ADDR
(HEX)
DESCRIPTION RANGE STEP VALUE
UNITS and
SCALE
FOR-MAT FACTORY DEFAULT
MOD 506
ACTUAL
VALUES
0E10 Step 1 Pickup Timer --- --- 0.1 x F1 ---
0E11 Step 2 Pickup Timer --- --- 0.1 x F1 ---
0E12 Step 3 Pickup Timer --- --- 0.1 x F1 ---
0E13 Step 4 Pickup Timer --- --- 0.1 x F1 ---
0E14 Step 1 Disable Timer --- --- 0.1 x F1 ---
0E15 Step 2 Disable Timer 0.1 x F1 ---
0E16 Step 3 Disable Timer --- --- 0.1 x F1 ---
0E17 Step 4 Disable Timer --- --- 0.1 x F1 ---
0E18 System Stabilization --- --- 0.1 x F1 ---
0E19 Low Voltage Detect --- --- 0.1 x F1 ---
MOD 506
SETPOINTS
1300 Step 1 Relay 0 to 4 1 --- F1 0 = OFF
1301 Step 1 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
1302 Step 1 Dropout Level
–32000 to
32000
1 kvar F2 0=0.0 kvar
1303 Step 1 Pickup Delay 1 to 600 1 min F1 10=1.0 min
1304 Step 1 Disable Time 1 to 600 1 min F1 50=5.0 min
1305 Step 2 Relay 0 to 4 1 --- F1 0 = OFF
1306 Step 2 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
1307 Step 2 Dropout Level
–32000 to
32000
1 kvar F2 0=0.0 kvar
1308 Step 2 Pickup Delay 1 to 600 1 min F1 10=1.0 min
1309 Step 2 Disable Time 1 to 600 1 min F1 50=5.0 min
130A Step 3 Relay 0 to 4 1 --- F1 0 = OFF
130B Step 3 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
130C Step 3 Dropout Level
–32000 to
32000
1 kvar F2 0=0.0 kvar
130D Step 3 Pickup Delay 1 to 600 1 min F1 10=1.0 min
130E Step 3 Disable Time 1 to 600 1 min F1 50=5.0 min
130F Step 4 Relay 0 to 4 1 --- F1 0 = OFF
1310 Step 4 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
1311 Step 4 Dropout Level
–32000 to
32000
1 kvar F2 0=0.0 kvar
1312 Step 4 Pickup Delay 1 to 600 1 min F1 10=1.0 min
1313 Step 4 Disable Time 1 to 600 1 min F1 50=5.0 min
1314 System Stabilization 1 to 600 1 min F1 50=5.0 min
1315
Low Voltage Detect
Level
30 to
65000
1 V F1 100 V
1316
Low Voltage Detect
Delay
5 to 6000 1 s F1 10=1.0 s
1317 Step Sequence 0 to 23 1 --- F42 0=“1,2,3,4”
CODE DESCRIPTION BITMAS
K
F42 Step Sequence Priority FFFF
0 = “1, 2, 3, 4” ---
1 = “1, 2, 4, 3” ---
2 = “1, 3, 2, 4” ---