6–20 PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 6: MONITORING
The alarm messages appear only when the alarm threshold has been exceeded for the
programmed time. When an alarm is assigned to an output relay, the relay can be set to be
unlatched or latched. When the alarm is set as unlatched, it automatically resets when the
alarm condition no longer exists. If the alarm is set as latched, a keypad reset or a serial
port reset is required.
The
SELF TEST ALARM occurs if a fault in the PQMII hardware is detected. This alarm is
permanently assigned to the alarm output relay and is not user configurable. If this alarm
is present, contact the GE Multilin Service Department.
6.3.2 Switch Status
PATH: ACTUAL VALUES Ö A2 STATUS ÖØ SWITCHES
MESSAGE
MAIN ANALOG INPUT
ALARM
MESSAGE
ALT ANALOG INPUT
ALARM
MESSAGE
CRITICAL SETPOINTS
NOT STORED
MESSAGE
CURRENT THD
ALARM
MESSAGE
VOLTAGE THD
ALARM
MESSAGE
PULSE INPUT 1
ALARM
MESSAGE
PULSE INPUT 2
ALARM
MESSAGE
PULSE INPUT 3
ALARM
MESSAGE
PULSE INPUT 4
ALARM
MESSAGE
TOTALIZED PULSES
ALARM
MESSAGE
TIME
ALARM
SWITCHES [Z] SWITCH INPUT A
STATE: Closed
MESSAGE
SWITCH INPUT B
STATE: Closed
MESSAGE
SWITCH INPUT C
STATE: Closed
MESSAGE
SWITCH INPUT D
STATE: Closed