CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL 5–29
FIGURE 5–2: Pulse Output Timing
5.3.6 Pulse Input
PATH: SETPOINTS ÖØ S2 SYSTEM SETUP ÖØ PULSE INPUT
• PULSE INPUT UNITS: This message allows the user to input a user defined 10
character alphanumeric unit for the pulse inputs (i.e. kWh). The unit will be used by all
pulse inputs including the totalized value. To enter the unit, perform the following
steps:
Z Allow access to setpoints by enabling setpoint access.
Z Select the
PULSE INPUT UNITS setpoint.
Z Use the
VA L U E keys to change the blinking character over the cursor. A
space is selected like a character.
Z Press the
ENTER key to store the character and advance the cursor to the
next position. To skip over a character press the ENTER key.
PULSE
WIDTH
OPENCLOSED
OPENOPEN
CLOSED
CLOSED
Normally Open (NO) Contact
Normally Closed (NC) Contact
STATUS STATUS
STATUS
PULSE INPUT [Z] PULSE INPUT
UNITS: Units
Range: 10 alphanumeric characters
MESSAGE
PULSE INPUT 1 VALUE:
1 Units
Range: 0 to 65000 in steps of 1
MESSAGE
PULSE INPUT 2 VALUE:
1 Units
Range: 0 to 65000 in steps of 1
MESSAGE
PULSE INPUT 3 VALUE:
1 Units
Range: 0 to 65000 in steps of 1
MESSAGE
PULSE INPUT 4 VALUE:
1 Units
Range: 0 to 65000 in steps of 1
MESSAGE
PULSE INPUT TOTAL:
1+2+3+4
Range: 1+2, 1+3, 1+4, 2+3, 2+4, 3+4,
1+2+3, 1+3+4, 1+2+4, 2+3+4,
1+2+3+4