6–16 PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
CHAPTER 6: MONITORING
• FREQUENCY: This message displays the frequency (in Hz). Frequency is calculated 
from the phase A-N voltage (when setpoint 
S2 SYSTEM SETUP ÖØ CURRENT/VOLTAGE 
CONFIGURATION ÖØ VT WIRING
 is “Wye”) or from phase A-B voltage (when setpoint VT 
WIRING is “Delta”). A value of “0.00” is shown if there is insufficient voltage applied to 
the PQMII’s terminals (less than 30 V on phase A).
• FREQ MIN: This message displays the minimum frequency measured as well as the 
time and date at which the minimum frequency occurred.
• FREQ MAX: This message displays the maximum frequency measured as well as the 
time and date at which the maximum frequency occurred. 
6.2.8 Pulse Input Counters
PATH: ACTUAL VALUES Ö A1 METERING ÖØ PULSE INPUT COUNTERS
• PULSE INPUT 1(4): These messages display the accumulated value based on total 
number of pulses counted since the last reset. One switch input pulse is equal to the 
value assigned in the 
S2 SYSTEM SETUP ÖØ PULSE INPUT ÖØ PULSE INPUT 1(4) VALUE setpoint. 
The units shown after the value are as defined in the 
PULSE INPUT UNITS setpoint in the 
same menu. The displayed value rolls over to “0” once the value “4294967295” 
(FFFFFFFFh) has been reached. To use this feature, the “C” (control) option must be 
installed and one of the PQMII switch inputs must be assigned to “Pulse Input 1(4)” 
function. The switch input will then count the number of closures or openings 
depending upon how the switch is configured; see 
Switch Inputs on page 5–21 for 
details. The minimum timing requirements are shown in FIGURE 6–2: Pulse Input 
Timing.
• PULSE IN 1+2+3+4: The totalized pulse input value is displayed here. The pulse inputs 
totalized is based on the 
S2 SYSTEM SETUP ÖØ PULSE INPUT ÖØ PULSE INPUT TOTAL setpoint.
• TIME OF LAST RESET: This message displays the time and date when the pulse input 
values were last cleared. The 
S1 PQMII SETUP ÖØ CLEAR DATA ÖØ CLEAR PULSE INPUT VALUES 
setpoint clears the pulse input values.
 PULSE INPUT [Z]
COUNTERS
PULSE INPUT 1 =
0 Units
MESSAGE
PULSE INPUT 2 =
0 Units
MESSAGE
PULSE INPUT 3 =
0 Units
MESSAGE
PULSE INPUT 4 =
0 Units
MESSAGE
PULSE INPUT 1+2+3+4
= 0 Units
MESSAGE
TIME OF LAST RESET:
12:00:00am 01/01/95