EasyManua.ls Logo

GE PQMII - Specifications

GE PQMII
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1–14 PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW
1.6 Specifications
Note
Specifications are subject to change without notice.
1.6.1 Inputs/Outputs
CURRENT INPUTS
Conversion:...................................................true RMS, 64 samples/cycle
CT Input: .........................................................1 A and 5 A secondary
Burden: ...........................................................0.2 VA
Overload: .......................................................20 × CT for 1 sec.
100 × CT for 0.2 sec.
Range:.............................................................1 to 150% of CT primary
Full Scale:.......................................................150% of CT primary
Frequency: ....................................................up to 32nd harmonic
Accuracy:.......................................................±0.2% of full scale at <1.20 x CT
VOLTAGE INPUTS
Conversion:...................................................true RMS, 64 samples/cycle
VT pri./sec.:....................................................120 to 72000 : 69 to 240, or Direct
VT Ratio: .........................................................1:1 to 3500:1
Burden: ...........................................................2.2 MΩ
Input Range:.................................................40 to 600 V AC
Full scale:
for VT input 150 V AC: ......................150 V AC
for VT input >150 V AC: ......................600 V AC
Frequency: ....................................................up to 32nd harmonic
Accuracy:.......................................................±0.2% of full scale
SWITCH INPUTS
Type:.................................................................dry contacts
Resistance:....................................................1000 Ω max ON resistance
Output:............................................................24 V DC at 2 mA (pulsed)
Duration: ........................................................100 ms minimum
ANALOG OUTPUT (0–1 MA)
Max. load: ......................................................2400 Ω
Max. output: .................................................1.1 mA
Accuracy:.......................................................±1% of full-scale reading
Isolation:.........................................................±36 V DC isolated, active source
ANALOG OUTPUT (4–20 MA)
Max. load: ......................................................600 Ω
Max. output: .................................................21 mA
Accuracy:.......................................................±1% of full-scale reading
Isolation:.........................................................±36 V DC isolated, active source
PULSE OUTPUT
Parameters:..................................................+kWh, –kWh, +kvarh, –kvarh, kVAh
Interval:...........................................................1 to 65000 in steps of 1
Pulse width: ..................................................100 to 2000 ms in steps of 10
Minimum pulse interval: ........................500 ms
Accuracy:.......................................................±10 ms

Table of Contents