CHAPTER 6: MONITORING
PQMII POWER QUALITY METER – INSTRUCTION MANUAL 6–21
To assist in troubleshooting, the state of each switch can be verified using these messages.
A separate message displays the status of each input identified by the corresponding
name as shown in the wiring diagrams in chapter 2. For a dry contact closure across the
corresponding switch terminals the message will read “Closed”.
6.3.3 Clock
PATH: ACTUAL VALUES Ö A2 STATUS ÖØ CLOCK
The current time and date is displayed in this message. The PQMII uses an internally
generated software clock which runs for approximately thirty days after the control power
has been removed. For instructions on setting the clock, see 5.2.6 Clock. The
S4 ALARMS/
CONTROL ÖØ MISCELLANEOUS ÖØ CLOCK NOT SET ALARM alarm occurs if power has been removed
for longer than thirty days and the clock value has been lost.
6.3.4 Programmable Message
PATH: ACTUAL VALUES Ö A2 STATUS ÖØ PROGRAMMABLE MESSAGE
A 40-character user defined message is displayed. The message is programmed using the
keypad or via the serial port using the EnerVista PQMII Setup Software. See 6.3.4
Programmable Message for programming details.
CLOCK [Z] TIME: 12:00:00am
DATE: Nov 21 2003
PROGRAMMABLE [Z]
MESSAGE
PHONE: 905-294-6222
www.GEmultilin.com