5–28 PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.3.5 Pulse Output
PATH: SETPOINTS ÖØ S2 SYSTEM SETUP ÖØ PULSE OUTPUT
kWh / kvarh / kVAh PULSE OUTPUT RELAY: Five pulse output parameters can be
assigned to the alarm or auxiliary relays. They are positive kWh, negative kWh, positive
kvarh, negative kvarh, and kVAh. Enter the desired relay to which each parameter is
assigned. Select “Off” if a particular output parameter is not required.
KWh / kvarh / kVAh PULSE OUTPUT INTERVAL: Enter the interval for the appropriate
quantity at which the relay pulse will occur. The pulse width is set by the
PULSE WIDTH
setpoint described below. If the pulse interval is set to “100 kWh”, one pulse will
indicate that 100kWh has been accumulated.
PULSE WIDTH: This setpoint determines the duration of each pulse as shown in the
figure below.
PULSE OUTPUT [Z] POS kWh PULSE OUTPUT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
POS kWh PULSE OUTPUT
INTERVAL: 100 kWh
Range: 1 to 65000 kWh in steps of 1
MESSAGE
NEG kWh PULSE OUTPUT
RELAY: Off
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
NEG kWh PULSE OUTPUT
INTERVAL: 100 kWh
Range: 1 to 65000 kWh in steps of 1
MESSAGE
POS
kvarh
PULSE OUTPUT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
POS
kvarh
PULSE OUTPUT
INTERVAL: 100
kvarh
Range: 1 to 65000 kvarh in steps of 1
MESSAGE
NEG
kvarh
PULSE OUTPUT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
NEG
kvarh
PULSE OUTPUT
INTERVAL: 100 kvarh
Range: 1 to 65000 kvarh in steps of 1
MESSAGE
kVAh
PULSE OUTPUT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
kVAh
PULSE OUTPUT
INTERVAL: 100 kVAh
Range: 1 to 65000 kVAh in steps of 1
MESSAGE
PULSE WIDTH:
100 ms
Range: 100 to 2000 ms in steps of 10