5–42 PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
positive/negative real power but no message will be displayed. This is intended for
process control.
POSITIVE/NEGATIVE REAL POWER LEVEL: When the three phase real power equals or
exceeds the level defined by this setpoint, an excess positive/negative real power
condition will occur.
POSITIVE/NEGATIVE REAL POWER DELAY: If the positive/negative real power equals
or exceeds the
POSITIVE/NEGATIVE REAL POWER LEVEL setpoint value for the time delay
programmed in this setpoint, an excessive positive/negative real power condition will
occur.
POSITIVE/NEGATIVE REACTIVE POWER RELAY: Positive and negative reactive power
level detection can either be disabled, used as an alarm, or as a process control. Set
this setpoint to “Off” if the feature is not required. Selecting “Alarm” activates the alarm
relay and displays an alarm message whenever a positive/negative reactive power
level exceeds the selected level. Selecting an auxiliary relay activates the auxiliary
relay for a set level of positive/negative reactive power but no message will be
displayed. This is intended for process control.
POSITIVE/NEGATIVE REACTIVE POWER LEVEL: When the three phase reactive power
equals or exceeds the level set by this setpoint, an excess positive/negative reactive
power condition will occur.
POSITIVE/NEGATIVE REACTIVE POWER DELAY: If the positive reactive power equals or
exceeds the
POSITIVE/NEGATIVE REACTIVE POWER LEVEL setpoint value for the time delay
programmed in this setpoint, an excessive positive reactive power condition will occur.