2–10 PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 2: INSTALLATION
Three-wire systems with voltages 600 V (L-L) or less can be directly connected to the PQMII
without VTs. Select the
S2 SYSTEM SETUP ÖØ CURRENT/VOLTAGE CONFIGURATION ÖØ VT WIRING: “3
WIRE DIRECT”
setpoint.
The PQMII voltage inputs should be directly connected using HRC fuses rated at 2 amps to
ensure adequate interrupting capacity.
FIGURE 2–7: Wiring Diagram 3-wire Direct (No VTs)