RT430-TM-EN-5
41
See details about log files access in Chapter 5.
Figure 22: Connection diagram of event input, used to verify synchronism signal
2.17 Type Test
TABLE 22: EMC tests were performed according to IEC 60255-26 referring to the following standards
IEC 61000-4-2:2008
6kV contact / 8KV air
IEC 61000-4-3:2006
10 V/m
IEC 61000-4-4:2012
2 KV @ 5KHz
IEC 61000-4-5:2005
Differential mode: 1KV
Common mode: 2KV
IEC 61000-4-6:2008
10V
IEC 61000-4-8:2009
30A/m continuos - 300A/m @ 1s.