Test level: 15 % of rated d.c. value
Test frequency: 120Hz, sinusoidal waveform.
Voltage oscillation frequency: 1MHz
Differential mode: 1kV peak voltage;
Common mode 2,5kV peak voltage
Shut-down ramp: 60s
Power off: 5m
Start-up ramp: 60s
Radiated emission
Limits:
30 to 230MHz - 50dB(μV/m) quasi peak at 3m
230 to 1000MHz - 57dB(μV/m) quasi peak at 3m
Radiated emission
The definition of the limit frequency is based on the maximum internal
frequency of the equipment. On RT430, the maximum internal frequency
is 100 MHz. For this case, the levels of CISPR 11 satisfy the normative
IEC 60255-26.
Conducted emission
Limits:
0.15 to 0.50MHZ - 79dB(μV) quasi peak; 66dB(μV) average
0.5 to 30MHz - 73dB(μV) quasi peak; 60dB(μV) average
TABLE 23: Safety tests
Inpulse - 5KV
Dielectric withstand - 3,3KVDC
Insulation > 100M Ω