EasyManua.ls Logo

GE TLE series 600 - Ventilation and Cooling

GE TLE series 600
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Critical Power
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
5.5 VENTILATION AND COOLING
Fig. 5.5-1 Installation on plain floor
Fig. 5.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
Contact your Dealer or the nearest Service Centre for appropriate solutions.
The below table indicates the heat dissipation at full Load at PF = 0.9 & 1 and charged Battery, up to
1000 m (3280 ft) altitude, for cooling air 25°C (77°F) to 30°C (86°F).
UPS model
Losses
Cooling air flow
VFI
eBoost™ (option)
VFI
PF = 0.9
PF = 1
PF = 0.9
PF = 1
PF = 0.9
PF = 1
TLE Series 600
20.7 kW
24.3 kW
6.5 kW
7.3 kW
6003 m
3
/h
7047 m
3
/h
TLE Series 800
27.7 kW
32.5 kW
8.7 kW
9.7 kW
8033 m
3
/h
9425 m
3
/h
NOTE !
Even when eBoost™ Operating Mode option is available, the ventilation and cooling
system shall be rated as for operation in VFI mode.
Air Extraction
Air Intake
TLES_600-800_S1_UPS ventilation_Raised floor_01GB
Air Intake
TLES_600-800_S1_UPS ventilation_Raised floor_01GB
Air Extraction

Table of Contents

Related product manuals