The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will
run in IEMi Operation Mode.
The IEMi Operation Mode has been disabled or the
programmed time is expired.
eBoost/IEMi ACTIVATION ALLOWED
eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
of the functions.
eBoost/IEMi ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited.
eBoost INHIBITED - LOW LOAD
eBoost™ Operation Mode inhibited due to minimal
load not reached.
Automatic Battery Test is not possible due to:
- No Mains Rectifier or Bypass.
- Battery not fully charged.
- Load is below 10% or above 80%.
Test is postponed for 1 week.
Inverter can be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
The Service Key validity period has expired.