115
ASCII: Data, which will send over the link as ASCII characters.
HEX: Hexadecimal values of the data
The word at address contains the value 1234h = 4660 decimal.
Example: Read Words, Function 04h, RTU Mode
Read one word at address 63h (= 99 decimal):
Query:
Byte
1
2
3
4
5
6
7
8
Meani
ng
silent
interval
>= 3.5
charact
ers
Slave
number
function
code
address of first
word to read
word count to
read
CRC
silent
interval
>= 3.5
charact
ers
high
byte
low
byte
high
byte
low
byte
low
byte
High
byte
RTU
HEX
[01]
[04]
[00]
[63]
[00]
[01]
[C1]
[D4]
Answer:
Byte
1
2
3
4
5
6
7
Meani
ng
silent
interval
>= 3.5
charact
ers
Slave
number
function
code
byte
count
Content
s of
the
word
CRC
Silent
interval
>= 3.5
charact
ers
RTU
HEX
high
byte
low
byte
low
byte
high
byte
[01]
[04]
[02]
[12]
[34]
[B4]
[47]
The word at address contains the value 1234h = 4660 decimal.
E.5. UPS Parameter
Standard UPS Address Description
Please note that this is just an example for a typical UPS, not every UPS has all these values,
some UPS may have more, some less. Please contact your UPS manufacturer to check which
variables are available and which requests are not supported.
Note: “Type U/S”: this defines whether the answer has an algebraic sign (math. +/-) or not. U
means “unsigned”. S means “signed”, this answer may be positive or negative.
Some clients (e. g. MODBUS Poll) use “MODBUS addresses” with a valid range of 0-
65535, but some other clients use the “MODBUS register” with a valid range of 1-65536. In this
case it is required to add a “1” to the MODBUS address you want to poll.
If you are using a PILLER UPS with a CS121 firmware version 4.29.3 or higher,
please take a look into the UPS user manual for the accordant MODBUS values. If you are
using a BACS system at the same time, no BACS values will be available via MODBUS.
Address
Type
Function
Name
Description
Len
gth
97
U
3 / 4
OUTPUT_VOLT0
Output Voltage Phase 1 in V
1
98
U
3 / 4
OUTPUT_VOLT1
Output Voltage Phase 2 in V
1