144
UPS service is started into the CS121. This event is always true, if the
CS121 is running and therefore ideal for permanent recurrent jobs
suitable like the forwarding of emails always after restart of the UPS or
to produce log file entries steady.
UPS RS232 communication lost, CS121 tries to restore the connection.
UPS RS232 communication restored
The autonomy of the battery has reached the defined threshold
"Battery Low". The UPS shutdown is pending. ADVICE: The RCCMD
shutdowns will be set into this event too, but without delay!
(Emergency shutdown, if batteries are to weak)
Output breaker open. UPS is isolated from load. No supply of the
consumers.
Output breaker closed. Load will be supplied.
Maintenance Breaker Closed
Maintenance breaker closed (active). Load will be supplied through the
grid directly.
Maintenance breaker open (inactive). Load will be supplied via the UPS.
Regular UPS protected operation.
Inverter breaker open. Load is not UPS protected!
Inverter breaker closed. Load will be supplied via the inverter. Normal
condition.
Battery breaker open. No battery buffering active!
Battery breaker closed. OK, normal condition.
New alarm, buzzer was activated.
An alarm has occured. Alarm LED at the UPS is flashing.
No more alarm is active. Alarm LED at the UPS is off.
Overtemperature of the UPS
Temperature of the UPS is back in normal range.
UPS output failure (e. g. voltage, frequency)
UPS overload, reduce load otherwise the UPS shutdown is pending
Bypass failure at input (e. g. voltage, frequency)