EasyManua.ls Logo

GF EA Series - Performing a factory reset; Help in case of faults; Error message indicator

GF EA Series
112 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instruction manual Help in case of faults
65
9.5 Performing a factory reset
When performing a factory reset, all previously saved positions will be deleted, and
a possible color inversion will be cancelled.
1. Open cover. To do so, loosen the 4 screws (torx size 20).
2. Press the SET + CW buttons.
The factory reset is performed.
3. Now the status feedback LED is blinking yellow and the Error Code „e“ is
shown .(Error in position detection) on the 7-segment display. All preciously stored
positions are deleted.
4. Readjusting the end positions, see Chapter “Adjusting end positions”.
5. As minimum requirement OPEN and CLOSE positions have to be adjusted
6. Reinstall the cover and fasten it with the 4 screws.
10 Help in case of faults
10.1 Error message indicator
7 segment display on the base board
In case of an error message, the following events may occur:
The LED flashes yellow (except during a power outage).
The ready-to-operate” signal (terminal 5.6 NO) drops.
The 7 segment display is illuminated on the base board, see ChapterAssignment of error
codes”.
If the monitoring accessories are installed, the LED on the BCD switch, of which the set
value has been exceeded, will also light up.