35
Function: Overrun correction function (only DES)
Menu item "2.2":
Automatic limit switch correction to achieve a constant CLOSE position.
Function Overrun correction
„.0“ Off
„.1“ On
Note: Overrun correction!
With DES limit switch only
Do not use with ground adjustment
Function: Reversing
Menu item "2.5":
Limiting of reversing following safety edge system activations via automatic closing.
If the set value is exceeded, automatic closing is deactivated and the "F2.2" fault indication is
displayed.
Note!
To reset fault "F2.2": Move to CLOSE final limit position