215
If there is no or not enough refrigerant inside the system to meet the operation startup
requirements, system will display U4 Refrigerant shortage protection and fail to continue with the
next progress. In this case, check for leakage or add refrigerant until error disappears.
09_Refrigerant
detection before
startup
System detects insufficient
refrigerant and stops to balance
the pressure lower than 0.3Mpa.
Step 14: Progress 10 is Outdoor unit valves detection before startup.
If master unit displays as follows, it means valves detection is being started.
10_
Outdoor unit valves
detection before
startup
Outdoor unit valves are
being inspected.
If the unit detects that valve status is not normal, it will display as follows:
10_
Outdoor unit valves
detection before
startup
Outdoor unit valves are
not fully opened.
In this case, check the big and small valves whether they are fully opened or not. After the
check, press SW6 to return to the previous step and restart valves detection.
If it is detected that valve status is normal, system will display as follows and automatically
enter the next progress.
10_
Outdoor unit valves
detection before startup
Outdoor unit valves are
opened properly.