EasyManua.ls Logo

Gree GMV-S280W/A-X

Gree GMV-S280W/A-X
391 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GMV5 Home DC Inverter Multi VRF Units
33
Outdoor unit: GMV-S280W/A-X
TCrepresents floor heating capacity of outdoor unit; PIrepresents power of outdoor unit
Water yielding temperature
Outdoor ambient
temperature
30
35
40
45
DB
WB
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
-7
-7.6
24.6
6.37
24.1
7.68
23.5
8.50
22.7
9.19
-5
-5.6
24.9
6.48
24.6
7.81
24.1
8.64
23.2
9.36
-3
-3.7
25.5
6.56
25.2
7.92
24.6
8.76
23.8
9.50
0
-0.7
26.6
6.17
26.0
7.71
25.5
8.79
24.4
10.40
3
2.2
28.0
5.76
28.0
7.20
28.0
8.21
25.2
9.36
5
4.1
28.0
5.55
28.0
6.93
28.0
7.90
28.0
9.01
7
6
28.0
5.33
28.0
6.67
28.0
7.60
28.0
8.67
9
7.9
28.0
5.14
28.0
6.42
28.0
7.32
28.0
8.35
11
9.8
28.0
4.95
28.0
6.19
28.0
7.05
28.0
8.05
13
11.8
28.0
4.77
28.0
5.97
28.0
6.80
28.0
7.76
15
13.7
28.0
4.61
28.0
5.77
28.0
6.57
28.0
7.51
7.6 Revision of length and fall difference of connecting pipe
GMV-S120WL/A-S
GMV-S140WL/A-S
GMV-S160WL/A-S
1) Change rate of cooling capacity 2) Change rate of heating capacity
GMV-S224W/A-XGMV-S280W/A-X
Hm(m)
40
20
30
10
Hp(m)
20
10
20
30
40
6040 80 100
50
L(m)
Hm(m)
40
20
30
10
Hp(m)
20
10
10
20 30
30
40
6040 50 70 80 11090 100
50
1.00
0.99
0.97
0.95
0.93
0.91
120
0.89
120
1) Change rate of cooling capacity 2) Change rate of heating capacity
Instruction:
3) Hp: Height difference (m) between two units when indoor unit is in lower position of
outdoor unit;

Table of Contents