GMV5 Home DC Inverter Multi VRF Units
380
Usage of Converter Configuring Software:
When the converter is working, hold the button "SET‖ for 5 seconds. Function LED will be
flickering, indicating that the converter has entered the baud rate setting mode. Then you can use
the converter configuring software to set the baud rate of converter. Baud rate is supported by the
converter (baud rate of air conditioner’s communication interface matches with the baud rate of
USB interface automatically):
Ex-factory defaulted baud rate: (unit: bps)
AC interface
Baud rate of AC interface
Baud rate of USB interface
CAN
20000
/
50000
self-adaptive
115200
HBS
57600
38400
RS485
9600
9600
Baud rate look-up table for RS485 interface (unit: bps)
RS485
interface
4800
9600
19200
38400
57600
115200
USB
interface
4800
9600
19200
38400
57600
115200
Baud rate look-up table for HBS interface (unit: bps)
HBS
interface
9600
19200
38400
57600
USB
interface
4800
9600
19200
38400
Baud rate look-up table for CAN interface (unit: bps)
CAN
interface
20000
50000
100000
125000