H3C S3600 Series Ethernet Switches Chapter 3 Installation
3-12
2) Fix the dust-proof shield by screws 3 and 4 by using a small flathead screwdriver,
see
Figure 3-16.
3) Enlace the two cables to the polarizing key at the back of the dust-proof shield
using the cable tie, see
Figure 3-16.
Screw 2
Screw 1
Cabinet
Connector
component
Screw 2
Screw 1
Cabinet
Connector
component
Figure 3-17 Fix RPS connector to the cabinet
Step 3: After installing connector component, directly insert the component into DC
socket on the cabinet, and then fix the screws 1 and 2 carried by the connector itself to
the appropriate holes on the cabinet socket using a small flathead screwdriver, see
Figure 3-17.
Step 4: Check that the RPS LED on the front panel of the switch is ON.
Caution:
z Before powering on the switch, connect the ground wire.
z The length of the DC power cord must be less than 3 m (9.8 ft.).
z Only the recommended PoE power supply can be used for the S3600-28P-PWR-SI,
S3600-28P-PWR-EI, S3600-52P-PWR-SI, and S3600-52P-PWR-EI. The –48 VDC
from the equipment room cannot be used directly. Otherwise, the device may be
damaged.