Refrigerant Filling Amount
Add the refrigerant according to the installation instruction of outdoor unit. The addition of R410A refrigerant must
be performed with a measure gage to ensure the specied amount while compressor failure can be caused by
lling too much or little refrigerant.
Connecting Procedures of Refrigerant Tubing
Proceed the are tube connecting operation to connect all the refrigerant tubes.
Dual wrenches must be used in the connection of indoor unit tubing.
Mounting torque refers to the right table
Outer Diameter of Tubing
(mm)
Mounting Torque
(N-m)
Increase mounting Torque
(N-m)
Ø6.35 11.8(1.2kgf-m) 13.7(1.4kgf-m)
Ø9.52 24.5(2.5kgf-m) 29.4(3.0kgf-m)
Ø12.7 49.0(5.0kgf-m) 53.9(5.5kgf-m)
Ø15.88 78.4(8.0kgf-m) 98.0(10.0kgf-m)
wrench
Cutting and Enlarging
Cutting or enlarging pipes should be proceeded by installation personnel according to the operating criterion if
the tube is too long or are opening is broken.
Vacuumizing
Vacuumize from the stop valve of outdoor units with vacuum pump. Refrigerant sealed in indoor machine is not
allowed to use for vacuumization.
Open All Valves
Open all the valves of outdoor units.
[NB: oil balancing stop valve must be shut up completely when connected one main unit.]
Checkup for Air Leakage
Check if there is any leakage at the connecting part and bonnet with hydrophone or soapsuds.