10
MODEL AB182MCERA AB242MCERA AB282MCERA
Cabinet
Cabinet coating type Galvanized Galvanized Galvanized
Cabinet salt spray test
duration
Hour 72 72 72
Control box IP class IP20 IP20 IP20
Construction
Sheet metal thickness 0.8 0.8 0.8
Drain pan material PS PS PS
Drain pan insulation 20 20 20
Drain pump option Standard 700mm Standard 700mm Standard 700mm
Branch outlet option No No No
Indoor wall
Material Hot zinc plate Hot zinc plate Hot zinc plate
Thickness mm 0.8 0.8 0.8
Double or single skin Single Single Single
Air lter
Material PP PP PP
Mesh 100 100 100
Pressure drop Pa 5 5 5
Piping dimension
Liquid pipe mm 6.35 9.52 9.52
Gas pipe mm 12.7 15.88 15.88
Drain hose mm 32 32 32
Panel
Model PB-950JB PB-950JB PB-950JB
Dimension mm 950*950*60 950*950*60 950*950*60
Packing mm 992*992*115 992*992*115 992*992*115
Net weight kg 6 6 6
Gross weight kg 7.5 7.5 7.5
Fresh air dimension mm / / /
Sound pressure level (H/M/L) dB (A) 34/32/30 35/34/31 37/35/31
Sound power level (H/M/L) dB (A) 48/46/44 49/48/45 51/49/45
Standard static pressure Pa 0 0 0
Indoor air ow (H/M/L) m³/h 1200/1010/820 1200/1010/820 1200/1010/820
Dimension (W*H*D) mm 840*240*840 840*240*840 840*240*840
Packing (W*H*D) mm 930/390/930 930/390/930 930/390/930
Net weight kg 30 30 30
Gross weight kg 32.5 32.5 32.5
Nominal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C)
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated