208
MODEL AD092MSERA(D) AD122MSERA(D)
Cabinet
Cabinet coating type Galvanized Galvanized
Cabinet salt spray test
duration
Hour 72 72
Control box IP class IP20 IP20
Construction
Sheet metal thickness 0.8 0.8
Drain pan material PS PS
Drain pan insulation 20 20
Drain pump option Standard 600mm Standard 600mm
Branch outlet option No No
Indoor wall
Material Hot zinc plate Hot zinc plate
Thickness mm 0.8 0.8
Double or single skin Single Single
Air lter
Material PP PP
Mesh 100 100
Pressure drop Pa 5 5
Piping
dimension
Liquid pipe mm 6.35 6.35
Gas pipe mm 9.52 12.7
Drain hose mm 25 25
Fresh air dimension mm Ф80 Ф80
Sound pressure level (H/M/L) dB (A) 30/27/24 27/23/20
Sound power level (H/M/L) dB (A) 44/41/38 41/37/34
Static pressure Pa 0/15/30 0/15/30
Indoor air ow (H/M/L) m
3
/h 550/430/370 480/420/360
Air outlet dimensions mm 640*90 640*90
Air return dimensions mm 760*152 760*152
Dimension (W*H*D) mm 850/420/185 850/420/185
Packing (W*H*D) mm 1045/540/270 1045/540/270
Net weight kg 17.5 17.5
Gross weight kg 22.5 22.5
Nominal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C)
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter. It is a sound pressure noise level.