EasyManua.ls Logo

Haier AB072MRERA - Page 218

Haier AB072MRERA
651 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
210
MODEL AD162MSERA(D) AD182MSERA(D) AD242MSERA(D)
Cabinet
Cabinet coating type Galvanized Galvanized Galvanized
Cabinet salt spray test
duration
Hour 72 72 72
Control box IP class IP20 IP20 IP20
Construction
Sheet metal thickness 0.8 0.8 0.8
Drain pan material PS PS PS
Drain pan insulation 20 20 20
Drain pump option Standard 600mm Standard 600mm Standard 600mm
Branch outlet option No No No
Indoor wall
Material Hot zinc plate Hot zinc plate Hot zinc plate
Thickness mm 0.8 0.8 0.8
Double or single skin Single Single Single
Air lter
Material PP PP PP
Mesh 100 100 100
Pressure drop Pa 5 5 5
Piping
dimension
Liquid pipe mm 6.35 6.35 9.52
Gas pipe mm 12.7 12.7 15.88
Drain hose mm 25 25 25
Fresh air dimension mm Ф80 Ф80 Ф80
Sound pressure level (H/M/L) dB (A) 32/29/26 33/30/27 36/33/30
Sound power level (H/M/L) dB (A) 46/43/40 47/44/41 50/47/43
Static pressure Pa 0/15/30 0/15/30 0/15/30
Indoor air ow (H/M/L) m
3
/h 600/540/460 800/690/580 930/850/750
Air outlet dimensions mm 640*90 960*90 960*90
Air return dimensions mm 760*152 1080*152 1080*152
Dimension (W*H*D) mm 850/420/185 1170/420/185 1170/420/185
Packing (W*H*D) mm 1045/540/270 1365/540/270 1365/540/270
Net weight kg 18.5 22.2 24
Gross weight kg 23.5 28.2 30
Nominal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C)
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter. It is a sound pressure noise level.

Table of Contents

Related product manuals