290
MODEL AD242MJERA AD282MJERA
Cabinet
Cabinet Coating Type Galvanized Galvanized
Cabinet Salt Spray Test
Duration
Hour 48 48
Control Box IP Class IP20 IP20
Construction
Sheet Metal Thickness 0.8 0.8
Drain Pan Material EPS EPS
Drain Pan Insulation HF-1 HF-1
Drain Pump Option mm 600 600
Branch Outlet Option NO NO
Indoor Wall
Material Hot zinc plate Hot zinc plate
Thickness mm 1.2 1.2
Double or Single Skin Single Single
Air Filter
Material PP PP
Mesh 100 100
Pressure Drop Pa 5 5
Piping
dimension
Liquid pipe mm 9.52 9.52
Gas pipe mm 15.88 15.88
Drain hose mm 31.5 31.5
Fresh air dimension mm / /
Sound pressure level (H/M/L) dB(A) 38/36/34 42/39/35
Sound power level (H/M/L) dB(A) 42/40/38 46/43/39
Standard static pressure Pa 50 50
Max. static pressure Pa 100 100
Indoor air ow (H/M/L) m
3
/h 1230/1090/950 1230/1090/950
Air outlet dimensions mm 800*160 800*160
Air return dimensions mm 850*220 850*220
Dimension (W*H*D) mm 1050/720/250 1050/720/250
Packing (W*H*D) mm 1170/860/340 1170/860/340
Net weight kg 33.1 33.1
Gross weight kg 40.6 40.6
Nominal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C)
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter. It is a sound pressure noise level.