392
Before completing the electrical connection, a gibbose connector shall be installed on the drainpipe as to provide 
it with a water inlet port. Then, if any leakage exists in the piping, check it to make the water ow of the drainpipe 
smooth.
5. Installation of Air Return & Air Exhaust Pipes
For the choice and installation of air return port, air return pipe, air exhaust port and exhaust pipe, please consult 
service personnel of Haier company. Calculate the design chart and exterior static pressure, and select the exhaust 
pipe with appropriate length and shapes.
•  The length difference between pipes should be limited to be less than 2:1;
•  Make the piping as short as possible;
•  Keep the min. elbow quantity;
•  Wind the heat insulating material around the ange between the main 
unit and the exhaust pipe for heat insulation and sealing. Install the piping 
before tting up the ceiling.
•  At least 2 meters air duct is needed at air inlet and air outlet.
•  Flexible connection is needed between indoor units and air duct.
•  ESP should be lower than 200 Pa.
6. Cautions in Installation of Air Return Pipe & Exhaust Pipe
•  It is recommended to use the blast pipes, which can be anti-condensation 
and absorb sound. (purchased at local shops)
•  Complete the installation of the blast pipes before tting up the suspended 
ceiling.
•  Heat insulation should be made for the blast pipes.
•  The special exhaust port should be arranged at the place where the air is 
distributed evenly.
•  An inspection hole should be left on the surface of the ceiling for future 
maintenance.
Insert the hose into
20mm-30mm of feed
pipe at bottom
Dismantle
rubber plug,
reinstall it after installation
Install drainpipe clamp
Main unitD
Check drainage via
transparent tube socket
Pour water into a
gibbose connector
Main unit of air
conditioner
Special exhaust
port (purchased at
local shop)
Exhaust pipe
(purchased
at local
shop)
Inspection
hole
Air return
pipe
(purchased
at local
shop)
Special air return
pipe (purchased at
local shop) with air
cleaner
Incorrect Incorrect Correct
Special exhaust port
positioning with bolt
Blast pipe
Air
Air
Rain pipe
Ceiling 
surface