Constant Air Volume Duct
Type Indoor Unit (AD*MQERA)
Indoor power supply wiring & signal wiring between indoor and outdoor & signal wiring between indoor.
                           Items
Total
Current of
Indoor Unite(A)
Cross 
Section 
(mm
2
)
Length
(m)
Rated 
Current of 
Overow 
Breaker(A)
Rated current of residual 
Circuit Breaker(A) 
Ground Fault 
Interruptor(mA)
Response time(S)
Cross Sectional Area of 
Signal Line
Outdoor-
indoor
(mm
2
)
Indoor-
indoor
(mm
2
)
<7 2.5 20 10 10 A, 30mA, 0.1S or below
≥7 and <11 4 20 16 16 A, 30mA, 0.1S or below
2 cores×0.75-2.0 mm
2
shielded line
≥11 and <16 6 25 20 20 A, 30mA, 0.1S or below
≥16 and <22 8 30 32 32 A, 30mA, 0.1S or below
≥22 and <27 10 40 32 32 A, 30mA, 0.1S or below
•  The electrical power line and signal lines must be fastened tightly.
•  Every indoor unit must have the ground connection.
•  The power line should be enlarged if it exceeds the permissible length.
•  Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of 
signal lines of outdoor units grounded at one point.
•  It is not permissible if the whole length of signal line exceeds 1000m.
Signal wiring of wired controller
Length of signal line (m) Wiring dimensions
≤ 250 0.75mm
2
×3 core shielded line
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 250m.