33
4-Way Cassette 
Type Indoor Unit
The combination of multiple indoor units can be controlled by wired controller or remote controller.
 
※
 Switching mode of wired control master unit/  wired  control  slave unit/ remote control types can be used for 
switching over 
※
Note: 
The wiring for the power line of  indoor  unit,  the  wiring between indoor and outdoor units as well as  the  wiring 
between indoor units:
                 Items
Total  
current of 
indoor units (A)
Cross 
section 
(mm²)
Length 
(m)
Rated  
current of  
overow  
breaker (A)
Rated current of residual circuit 
breaker (A)
Ground fault interrupter (mA) 
Response time (S)
Cross sectional  
area of signal line
Outdoor 
-indoor (mm²)
Indoor 
-indoor (mm²)
<10   2 20 20 20 A, 30 mA, 0.1S or below
2 cores×(0.75-2.0)mm
2
 
shielded line
≥10 and <15 3.5 25 30 30 A, 30 mA, 0.1S or below
≥15 and <22  5.5 30 40 40 A, 30 mA, 0.1S or below
≥22 and <27   10 40 50 50 A, 30 mA, 0.1S or below
※
 
The electrical power line and signal lines must be fastened tightly.
※
 Every indoor unit must have the ground connection.
※
 The power line should be enlarged if it exceeds the permissible length.
※
 Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of
     signal lines of outdoor units grounded at one point. 
※
 It is not permissible if the whole length of signal line exceeds 1000m.
Signal wiring of wired controller
Length of signal line (m) Wiring dimensions
≤ 250 0.75mm
2
×3 core shielded line
※
 
The shielding lay of the signal line must be grounded at one end.
※
 
The total length of the signal line shall not be more than 250m.
                            Setting 
                              mode
Socket/dip 
switch
Wired control master unit Wired control slave unit  Remote control
SW01-[1][2][3][4] All OFF [0][0][0][1] All OFF
CN21 socket Null Null
Connect to remote 
receiver
Terminal block (control)
A, B, C connect with wired 
controller
B, C connect with wired 
controller
A, B, C Null