404
MODEL AD302MHERA AD382MHERA AD482MHERA
Cabinet 
Cabinet coating type Galvanized Galvanized Galvanized
Cabinet salt spray test 
duration 
Hour 72  72  72 
Control box IP class IP20 IP20 IP20
Construction
Sheet metal thickness 1 1 1
Drain pan material PS PS PS
Drain pan insulation 20 20 20
Drain pump option Optional KT-NP01 Optional KT-NP01 Optional KT-NP01
Branch outlet option No No No
Indoor wall
Material Hot zinc plate Hot zinc plate Hot zinc plate
Thickness mm 1 1 1
Double or single skin Single Single Single
Air lter  
Material PP PP PP
Mesh 100 100 100
Pressure drop Pa 5 5 5
Piping 
dimension
Liquid pipe mm 9.52 9.52 9.52
Gas pipe mm 15.88 15.88 15.88
Drain hose mm 32 32 32
Fresh air dimension mm 1100*255 1100*255 1100*255
Sound pressure level (H/L) dB(A) 45/43/40 45/43/40 45/43/40
Sound power level (H/L) dB(A) 58/53/50 58/53/50 58/53/50
Standard static pressure Pa 100 100 100
Max. static pressure Pa 196 196 196
Indoor air ow (H/M/L) m
3
/h 1560/1412/1133 1600/1448/1162 2100/1901/1525
Air outlet dimensions mm 853*255 853*255 853*255
Air return dimensions  mm 1100*255 1100*255 1100*255
Dimension (W*H*D) mm 1355*360*876 1355*360*876 1355*360*876
Packing (W*H*D) mm 1378*405*938 1378*405*938 1378*405*938
Net weight   kg 62 62 62
Gross weight   kg 77 77 77
Nominal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C) 
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated 
sound intensity meter. It is a sound pressure noise level.