450
Pipe Materials & Specications
Refrigerant Recharge Amount
Recharge the refrigerant according to the installation instruction of outdoor unit. The addition of R410Arefrigerant 
must be performed with a measure gage to ensure the specied amount or compressor failure can be caused by 
too much or less refrigerant.
Connecting Procedures of Refrigerant Tubing
Proceed the are tube connecting operation to connect all the refrigerant tubes.
Dual wrenches must be used in the connection of indoor unit tubing.
Mounting torque refers to the right table
Cutting and Enlarging
Vacuumizing
Open All Valves
Checkup for Air Leakage
Cutting or enlarging pipes should be proceeded by 
installation personnel according to the operating 
criterion if the tube is too long or flare opening is
broken.
Vacuumize from the stop valve of outdoor units with 
vacuum pump. Refrigerant sealed in indoor machine 
is not allowed to use for vacuumization.
Open all the valves of outdoor units. [NB: oil 
balancing stop valve must be shut up completely 
when connected one master unit.]
Check if there is any leakage at the connecting part 
and bonnet with hydrophone or soapsuds.
Connecting
1. Connecting circular terminals:
The connecting method of circular terminal is 
shown in the Fig. Take off the screw, connect it to 
the terminal tier after heading it through the ring at 
the end of the lead and then tighten it.
2. Connecting straight terminals:
The connection methods for the circular terminals 
are shown as follows: loosen the screw before 
putting the line terminal into the terminal tier, tighten 
the screw and conrm it has been clamped by 
pulling the line gently.
3. Pressing connecting line
After connecting line is completed, press the 
connecting line with clips which should press on the 
protective sleeve of the connecting line.
Model AD482MPERA AD722MPERA, AD962MPERA
Pipe Size (mm)
Gas Pipe Φ15.88 Φ25.4
Liquid Pipe Φ9.52 Φ9.52
Pipe Material Phosphor deoxy bronze seamless pipe (TP2) for air conditioner
Outer diameter of tubing (mm) Mounting torque
Φ9.52 40~50N.m
Φ15.88 90~120N.m
Φ19.05 100~140N.m
Φ25.4 --