453
Fresh Air Type
Indoor Unit
Note:
The wiring for the power line of indoor unit, the wiring between indoor and outdoor units as well as the wiring
between indoor units:
                   
              Items
Total  
current of 
indoor units (A)
Cross 
section 
(mm
2
)
Length 
(m)
Rated  
current of  
overow  
breaker (A)
Rated current of residual circuit 
breaker (A)
Ground fault interrupter (mA) 
Response time (S)
Cross sectional  
area of signal line
Outdoor
-indoor (mm
2
)
Indoor 
-indoor (mm
2
)
<10   2 20 20 20 A, 30 mA, 0.1S or below
2 cores×(0.75-2.0)
mm
2
 shielded line
≥10 and <15 3.5 25 30 30 A, 30 mA, 0.1S or below
≥15 and <22  5.5 30 40 40 A, 30 mA, 0.1S or below
≥22 and <27  10 40 50 50 A, 30 mA, 0.1S or below
 The electrical power line and signal lines must be fastened tightly.
 Every indoor unit must have the ground connection.
 The power line should be enlarged if it exceeds the permissible length.
 Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side 
     of signal lines of outdoor units grounded at one point. 
 It is not permissible if the whole length of signal line exceeds 1000m.
The combination of multiple indoor units can be controlled by wired controller or remote controller.
Switching mode of Wired control master unit/ Wired control slave unit/ remote control types can be used for 
switching over 
                            Setting 
                              mode
Socket/dip 
switch
Wired control master unit Wired control slave unit  Remote control
SW01-[1][2][3][4] All OFF [0][0][0][1] All OFF
CN21 socket Null Null
Connect to remote 
receiver
Terminal block (control)
A, B, C connect with wired 
controller
B, C connect with wired 
controller
A, B, C Null
Signal wiring of wired controller
Length of signal line (m) Wiring dimensions
≤ 250 0.75mm
2
×3 core shielded line
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 250m.