39
360
O
C Smart Air Flow 
Cassette Type Indoor Unit
Model AB162MRERA AB182MRERA AB242MRERA
Cabinet 
Cabinet coating 
type
Galvanized   Galvanized   Galvanized  
Cabinet salt spray 
test duration 
Hour 100 100 100
Control box IP class IP40 IP40 IP40
Construction
Sheet metal 
thickness
0.8 0.8 0.8
Drain pan material PS PS PS
Drain pan insulation 20 20 20
Drain pump option Standard 1200mm Standard 1200mm Standard 1200mm
Branch outlet option No No No
Indoor wall
Material Hot zinc plate Hot zinc plate Hot zinc plate
Thickness mm 0.8 0.8 0.8
Double or single 
skin
Single Single Single
Air lter  
Material PP PP PP
Mesh 100 100 100
Pressure drop Pa 5 5 5
Piping 
dimension
Liquid pipe mm 6.35 6.35 9.52
Gas pipe mm 12.7 12.7 15.88
Drain hose mm Φ25 Φ25 Φ25
Panel
Model  PB-950KC PB-950KC PB-950KC
Dimension mm 950/950/50 950/950/50 950/950/50
Packing mm 1013/1025/123 1013/1025/123 1013/1025/123
Net weight   kg 6.5 6.5 6.5
Gross weight   kg 9 9 9
Fresh air dimension mm / / /
Sound pressure level (H/M/L) dB(A) 32/29/27  33/30/29  35/34/31
Sound power level (H/M/L) dB(A) 46/43/41 47/44/43 49/48/45
Standard static pressure Pa 0 0 0
Indoor air ow (H/M/L) m
3
/h 1000/810/620 1000/810/620 1380/1190/1000
Dimension (W*H*D) mm 840/840/183 840/840/183 840/840/204
Packing (W*H*D) mm 983/983/268 983/983/268 983/983/290
Net weight   kg 28 28 29
Gross weight   kg 31 31 32
Norminal condition: indoor temperature (cooling): 27°C DB/19°C  WB, indoor temperature (heating): 20°C DB 
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB. The noise 
level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound 
intensity meter. It is a sound pressure noise level.