525
High Wall Type
Indoor Unit (N platform)
MODEL
AS242MNERA  AS282MNERA AS302MNERA
AS242MFERA  / /
Cabinet 
Cabinet Coating Type Plastic Plastic Plastic
Cabinet Salt Spray Test 
Duration 
Hour / / /
Control Box IP Class IP20 IP20 IP20
Construction
Sheet Metal Thickness / / /
Drain Pan Material ABS ABS ABS
Drain Pan Insulation 15 15 15
Drain Pump Option no no no
Branch Outlet Option no no no
Indoor Wall
Material Plastic Plastic Plastic
Thickness mm / / /
Double or Single Skin Single Single Single
Air Filter  
 Material PP PP PP
 Mesh 100 100 100
 Pressure Drop Pa 5 5 5
Piping 
dimension
Liquid pipe mm 9.52 9.52 9.52
Gas pipe mm 15.88 15.88 15.88
Drain hose mm 16.8 16.8 16.8
Fresh air dimension mm / / /
Sound pressure level (H/M/L) dB(A) 44/40/36 48/43/40 49/44/41
Sound power level (H/M/L) dB(A) 58/56/54 60/57/53 61/58/54
Standard static pressure Pa 0 0 0
Indoor air ow (H/M/L) m
3
/h 1010/920/800 1500/1400/1300 1600/1500/1400
Dimension (W*H*D) mm 1115/243/336 1316/270/365 1316/270/365
Packing   (W*H*D) mm 1206/342/418 1403/384/463 1403/384/463
Net weight   kg 16.5 21.5 21.5
Gross weight   kg 20.1 26.0 26.0
Nominal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating): 20DB (°C) 
Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated 
sound intensity meter. It is a sound pressure noise level.