High Wall Type
Indoor Unit (N platform)
Recommended: One wired controller controls more than one indoor unit (limited in high walls) 
Not recommended: One wired controller controls more than one indoor unit (ordinary indoors)
High wall wired controller wiring instruction:
1. One wired controller controls one high wall unit  (one  to  one),  connect the wires of wired controller to CN22 
terminal on PCB directly.
2. Two wired  controllers  control one high wall  unit  (two to one), connect  the  wires of wired controller  1  and 2 
respectively to CN22 and CN22-1 on PCB.
3. One wired controller controls more than one unit (one to more), limited in high wall units is recommended and 
mixed different type indoor units is not recommended. It’s easy to do wrong wiring when there’re many different 
type indoors.
If you choose one to more (mixed different type indoor units), please follow the principles below:
a. The communication wires of wired controller inlet or outlet high wall units are 3 cores. It means to connect all the 
wires "ABC".
b. When one wired controller connects to more indoors, all the wires between terminals are 3 cores. When other 
indoor units are slave ones of wired controller, for AC fan motor indoor unit connects B,C terminal, for DC fan 
motor indoor unit connects A,B,C teiminal. 
c. When the  "A" wire is  not connect to  indoors which are  the  slave ones  of  wired controller, please  do  some 
insulation on it and avoid touching other electric circuit.
 Ordinary indoor
(AC or DC fan motor)
Wired
controller
A B C
  Ordinary indoor
      (AC fan motor)
CN22 CN22-1 CN22 CN22-1
  Ordinary indoor
     (DC fan motor)
   High wall  High wall
A B C A B C A B C A B C A B CA B C