582
Note: For fresh air (AD*MPERA) the 0151800113 PCB dip switch setting as follows
(1) Description of SW01
SW01_1 
SW01_2 
SW01_3 
SW01_4
Wired control address
[1] [2] [3] [4] Wired control address
OFF OFF OFF OFF Master unit in group control
OFF OFF OFF
ON Slave unit 1 in group control
OFF OFF
ON OFF Slave unit 2 in group control
OFF OFF
ON ON Slave unit 3 in group control
… … … … ……
ON ON ON ON Slave unit 15 in group control
SW01_5 
SW01_6 
SW01_7 
SW01_8
Indoor unit 
capacity
[5] [6] [7] [8] Indoor unit capacity
OFF OFF OFF OFF 5HP (AD482MPERA)
OFF OFF OFF
ON 8HP (AD722MPERA)
OFF OFF
ON OFF 10HP (AD962MPERA)
(3) Description of SW03
SW03
Set the 
communication 
and central 
control address 
by dip switch 
(*Note 2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
 address
Central control 
address
ON OFF OFF OFF OFF OFF OFF OFF
0 
(default)
0 
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … …
Set the address by wired controller 
or automatically (default)
(2) CN41,CN42,CN43,CN44 plug explanation
CN41
Set address by 
wired controller 
or automatically 
(when SW03_1 is 
OFF)
OFF
Allow the wired controller to set the indoor address, after restart, the indoor 
address need to reset
ON
Allow the wired controller to set the indoor address, after restart, the indoor 
address which is set by wired control is same as before and needn't to reset
CN42 
CN43 
CN44
Indoor
type
CN44 CN42 CN43 Indoor type
OFF
ON OFF Fresh air unit
(4) SW07 are reserved functions,  factory setting are all ON and cannot be changed at random.
(5) SW08 (J1-J8) are reserved functions,  factory setting are all ON and cannot be changed at random.
Note:
OFF: the plug is open circuit
ON: the plug is short circuit