585
Dip Switch Setting
(2) Denition and description of SW03
Note 2:
• Set the address by dip switch when connecting the centralized controller or gateway or charge system.
• Central control address =communication address + 0 or +64.
• SW03_ 2=OFF, Central control address =communication address+0=communication address.
• SW03_ 2=ON, Central control address = communication address+64 (applies when
 central controller is used and there are more than 64 indoor units).
• When the 0151800161 and 0010451181A  PCB in one system, address must be set by dip switch. Set 
SW03_1=ON and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are address 
codes which are set according to actual address.
• Address setting function of wired controller for slim duct is unavailable.
(3) Denition and description of SW08
SW08_1
ON One by one
WIFI control mode
OFF One by multi
SW08_2
ON
Generally room card is disabled and there is no linkage 
control in the unit with total heat exchanger
Room card contact, total heat exchanger 
linkage
OFF
Room card is enabled, there is linkage control in the 
unit with total heat exchanger
SW08_3
ON General (default)
Selection of indoor unit priority
OFF High priority 
SW08_4
ON Ordinary unit
Isothermal dehumidication type indoor 
units selection
OFF Isothermal dehumidication unit
SW03
Set the 
communication 
and central 
control address 
by dip switch(note 
2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
 address
Central control 
address
ON OFF OFF OFF OFF OFF OFF OFF
0 
(default)
0 
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … … Set the address automatically (default)