588
SW03 is used to set indoor unit address
SW08
SW03
Set the
communication
and central
control address
by dip switch
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
address
Central control
address
ON OFF OFF OFF OFF OFF OFF OFF 0(default) 0(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … …
Set the address automatically
(default)
SW08_1 WIFI control mode
ON One by one (default)
OFF One by multi
SW08_2 Room card
ON Room card is unavailable (default)
OFF Room card is available
SW08_3 Dual heat source
ON No dual heat source control (default)
OFF Dual heat source control
SW08_4
Operation mode displayed on
wired controller
ON [auto] [fan] [cooling] [dehumidication] [heating]
OFF [fan] [cooling] [dehumidication]