593
Dip Switch Setting
LED light introduction:
• LED1, LED2: communication lamp between indoor unit and wired controller.
  These two lamps icker alternately under normal condition; once occurs the communication faulty, these
  two lamps will light or not light at the same time.
• LED3, LED4: communication lamp between indoor unit and outdoor unit.
  These two lamps icker alternately under normal condition; once occurs the communication faulty, these
  two lamps will light or not light at the same time.
• LED5: malfunction lamp of indoor unit.
  This lamp not light under normal condition; once indoor unit occurs malfunction this lamp will icker, icker
  times indicate the corresponding failure code.
Dip switch introduction
(1) Indoor address setting when in group control by wired controller: SW01
SW01
Description
[ 1 ] [ 2 ] [ 3 ] [ 4 ] [ 5 ] [ 6 ] [ 7 ] [ 8 ]
OFF OFF OFF OFF —— —— —— —— Wired controller address=1
OFF OFF OFF
ON —— —— —— —— Wired controller address=2
—— —— —— —— —— —— —— —— ——
ON ON OFF ON —— —— —— —— Wired controller address=15
ON ON ON ON —— —— —— —— Wired controller address=16
—— —— —— —— OFF OFF OFF OFF Indoor horse power=0.6HP
—— —— —— —— OFF OFF OFF
ON Indoor horse power=0.8HP (AB072MBERA)
—— —— —— —— OFF OFF
ON OFF Indoor horse power=1.0HP (AB092MBERA)
—— —— —— —— OFF OFF
ON ON Indoor horse power=1.2HP(AB122MBERA)
—— —— —— —— OFF
ON OFF OFF Indoor horse power=1.5HP
—— —— —— —— OFF
ON OFF ON Indoor horse power=1.7HP (AB162MBERA)
—— —— —— —— OFF
ON ON OFF Indoor horse power=2.0HP (AB182MBERA)
—— —— —— —— OFF
ON ON ON Indoor horse power=2.5HP
—— —— —— ——
ON OFF OFF OFF Indoor horse power=3.0HP
—— —— —— ——
ON OFF OFF ON Indoor horse power=3.2HP
—— —— —— ——
ON OFF ON OFF Indoor horse power=4.0HP
—— —— —— ——
ON OFF ON ON Indoor horse power=5.0HP
—— —— —— ——
ON ON OFF OFF Indoor horse power=6.0HP
—— —— —— ——
ON ON OFF ON Indoor horse power=8.0HP
—— —— —— ——
ON ON ON OFF Indoor horse power=10.0HP
—— —— —— ——
ON ON ON ON Indoor horse power=15.0HP
(2) Indoor address setting when in central control by central controller: SW02 (only on the master unit).
SW02
Description
[1] [2] [3] [4] [5] [6] [7] [8]
—— OFF OFF OFF OFF OFF OFF OFF Central control address=0
—— OFF OFF OFF OFF OFF OFF
ON Central control address=1
—— —— —— —— —— —— —— —— ——
——
ON ON ON ON ON ON OFF Central control address=26
——
ON ON ON ON ON ON ON Central control address=27
OFF Set central control address by wired controller
ON Forbidden to set address by wired controller