Dip Switch Setting
(7) Filter cleaning time selection:SW07-6
SW07-6 Function
ON 2500 hrs
OFF  120 hrs
(8) Operation mode changeover of wired controller (SW07-7, SW07-8)
SW07-8 SW07-7 Function
OFF OFF [AUTO] [FAN] [COOL] [DRY] [HEAT]
OFF
ON [FAN] [COOL] [DRY] [HEAT] [ELECTRIC HEAT]
ON OFF [FAN] [COOL] [DRY]
ON ON [FAN] [COOL] [DRY] [HEAT]
(9) Air volume: SW08-1 
SW08-1 Function
ON Normal operation
OFF Air volume is fixed ( for duct unit)
(10) In heating, fan speed selection:SW08-2
SW08-2 Function
ON Normal operation
OFF Run at mid. speed when in heating high speed
(11) 26
O
C lock function (SW08 3): in heating mode, though set temp. exceeds 20
O
C, count as 20
O
C; in 
cooling mode, though set temp. is below 26
O
C, count as 26
O
C.
SW08-3 Function
ON Normal mode
OFF 26
O
C lock is available
(12) Indoor priority selection (SW08-4)
SW08-4 Function
ON Normal mode
OFF Indoor priority is higher
(13) Room card function selection (SW08-5)
SW08-5 Function
ON Room card is available
OFF Room card is unavailable
(14) Wired control/remote control selection: SW08-6
SW08-6 Function
ON Wired control type
OFF Remote control type