615
Dip Switch Setting
(B) Denition and description of SW03
Note 2:
Set the address by dip switch when connecting the centralized controller or gateway or charge system.
Address of centralized controller =communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication address+0=communication address SW03_
2=ON, address of centralized controller=communication address+64 (applies when centralized controller is used
and there are more than 64 indoor units)
SW03
Set the
communication
and central
control address
by dip switch
(*Note 2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
address
Central control
address
ON OFF OFF OFF OFF OFF OFF OFF
0
(default)
0
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
ON ON ON ON ON ON ON ON 63 127
OFF
Set the address by wired controller
or automatically (default)