615
Dip Switch Setting
(B) Denition and description of SW03
Note 2:
•  Set the address by dip switch when connecting the centralized controller or gateway or charge system.
•  Address of centralized controller =communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication address+0=communication address SW03_ 
2=ON, address of centralized controller=communication address+64 (applies when centralized controller is used 
and there are more than 64 indoor units)
SW03
Set the 
communication 
and central 
control address 
by dip switch 
(*Note 2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
 address
Central control 
address
ON OFF OFF OFF OFF OFF OFF OFF
0 
(default)
0 
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … …
Set the address by wired controller 
or automatically (default)